RITZ indoor medium-voltage current transformers to the DIN 42600 standard dimensions, interchangeable in switchgear: 3.6 to 40.5 kV, primary currents up to 4,000 A.

RITZ DIN-design current transformer

Product Overview

DIN-design current transformers follow the DIN 42600 dimensions and fixing points, so they are interchangeable in medium-voltage switchgear. RITZ offers small (part 4), large (part 5) and narrow (part 8) designs from 3.6 to 40.5 kV.

The representative GSWS 12/24 is a narrow block-type CT to DIN 42600 part 8: fully cast in brown epoxy resin, with 1 or 2 cores (more on request) and metering and protection classes. The data below are for the GSWS 12/24.

Technical Data

Data for the GSWS 12/24

Voltage level
12, 17.5, 24 kV
Primary current
5 – 2,500 A
Secondary current
1 A or 5 A
Cores
1 or 2 (more on request)
Accuracy class
0.2 FS10, 0.2S FS10, 0.5 FS5, 0.5S FS5, 1 FS5, 5P, 10P
Burden
2.5 – 30 VA per core
Thermal short-time current
10 – 100 kA for 1 s
Extended current rating
120%
Insulation
Fully cast brown epoxy resin, class E (120 °C); silicone-free option
Frequency
50 / 60 Hz
Ambient
-5 to +40 °C

Reference data as published by the manufacturer. Contact Ha Thanh for help choosing the right model.

Models and Versions

  • GSWS 12/24Block type, narrow, DIN 42600 part 8, 12–24 kV
  • ASSNarrow, DIN 42600 part 8, 12–40.5 kV
  • ASNLarge, DIN 42600 part 5, 12–36 kV
  • GSW 10/20/30Large, DIN 42600 part 5, 10–30 kV
  • GSW 3.6/12Small, DIN 42600 part 4, 3.6–12 kV
  • GSS / GSSOHigh-current CTs, 100–4,000 A

Documents

Need a catalogue, drawing or datasheet for this product? Contact Ha Thanh for documents.